Multi-line 300 PPU 300 ver. 1.x.x.

该软件适用于以下 DEIF 产品:

将要下载 1.0.4.1

自上一版本以来实现的主要变化如下:

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.
 

版本 日期 描述

1.0.4.1

04/03/2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.
 

1.0.4.1

19/11/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

  • No changes

 

 

1.0.4.0

06/07/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

New features:

  • Now possible to use 16 controllers in single line

DU 300

  • No changes

 

1.0.3.0

20/04/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300 

New features:

  • CODESYS add-on
  • Frequency-dependent droop regulation
  • Support of GAM3.2 module with stand-alone possible
  • Able to abort "Lamp test" dialogue box
  • Power ramp configuration improved for better user experience
  • Selectable offsets for fixed P, Q and CosPhi regulation
  • Alarms made available in custom logic
  • Analogue I/O made available in custom logic
  • Parameter values made available in custom logic
  • Use external analogue signal as regulator set point
  • Alarm for F/V not OK made independent of GOV/AVR configuration
  • Power regulator set point range extended to -100 % to +100 %
  • GOV/AVR status display on PICUS and display
  • Regulation on SG 
  • Freeze regulation
  • Support of IOM3.4
  • Analogue value compare and operate function in custom logic

Changes: 

  • Optimised menu layout for better user experience
  • Improved ACM firmware update sequence

Corrections:

  • Compact breaker, optimised spring load sequence
  • "Blackout detection mismatch" functionality corrected
  • Fixed missing trip alarms
  • Manual regulation not possible with certain regulator settings
  • Fixed that "GB open-and-stop command" was ignored
  • Fixed that running detection by means of digital input could be delayed (affecting "Engine ready LED")
  • Fixed that in manual regulation mode, relay output could sometimes be left in "activated" state
  • Fixed that "Remove start" input could cause unintended short activation of crank relay
  • Fixed that cancelling a stop sequence could result in engine stopping anyway
  • Fixed that command "Open generator breaker and stop engine" could leave engine running
  • Fixed that running detection would not terminate crank timer
  • Fixed that alarms "GOV and AVR regulation error" would not be triggered
  • Alarms are always shown, even if configured as "suppressed"
  • Active start block alarm can no longer abort cooldown sequence
  • Genset temperature power derate functionality improved
  • "Start engine and close GB" command is now blocked by "Block engine start" command
  • Alarm on controller with breaker feedback error could result in breaker opening and engine stopping
  • DG suddenly becoming last controller on busbar during de-load, would trip its breaker
  • Detection of "Vector mismatch" improved
  • Fixed that "Freeze regulation" could leave relay output in "activated" state
  • Fixed that "BTB trip" command did not cancel synchronisation
  • Engine state in switchboard will now resolve to "Ready" instead of "Not Ready"

DU 300

New features:

  • Livedata configurator (View design)
  • Regulator screen (GOV/AVR)
  • Livedata dynamic reload integration
  • Message box popup

Changes:

  • Added display specific support for introspecting memory data
  • Update ID and labels on pair screen when entering the screen
  • Custom curves max precision changed from 2 to 8
  • Support for REST 1.0.4.0
  • Improvement to log output
  • Added direction to command list

Corrections:

  • DU relay not working
  • ML300 Backwards compatibility issues of DU
  • Parameter graph, special case fail
  • Livedata scales are not appearing
  • Event log was not telling which "command" (button) was pressed.
  • Blocking pop-up on DU 300 if controller software does not match.
  • Counter pop-ups now working correctly.
  • Display alarm list deadlock removed.
  • DU 300 able to change from service mode to app mode.
  • Inhibit counter on the parameters was showing wrong number of inhibits
  • Comma insted of dot between the (rack#,slot#) presentation of card name
  • Identify did not work when logged on
  • Corrections to dynamic reload of livedata
  • Corrections to eventlog navigation
  • Update value list on changes
  • Applying broadcast storm filter on startup
  • Display not showing Priority
  • Pair controller not working correctly with rework.

 

1.0.2.0

29/09/2017

New features:

  • Acces to all alarm status information from CODESYS
  • Extended status information for alarm functionblocks in CODESYS   

Changes: 

  • Software mismatch on hardware module(s) alarm only occur if first, second or third digit on IO card version is changed
  • New EIM 3.1 software 2.0.1.0

1.0.1.0

25/08/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.6.0

PPU 300 

New features:
   1  - 4 directional over-current alarms have been added to BTB (ANSI 67).
   2  - 2 directional over-current alarms have been added to SC and SG (ANSI 67).
   3  - Support of lamp test function.
   4  - Support of controller identify function.
   5  - Active regulator mode will be deactivated if a new is requested.
   6  - Additional information regarding alarms, breaker-, busbar- and generator status made available on Modbus.
   7  - Added "Critical process error"" alarm.
   8  - Last DG will trip if no other feeders are closed in the plant.

Changes:
   1  - "Power supply" parameter menu renamed to "Hardware".
   2  - "Network" parameter group moved to "Hardware" instead of "Utility". 
   3  - "Reset ratio" renamed to "Hysteresis" for protection alarms.
   4  - General check that "Nominal settings" cannot be configured to 0.
   5  - "Fixed power factor" renamed to "Fixed CosPhi".
   6  - "Analog" renamed to "Analogue".
   7  - "System not OK" alarm action is changed to "Warning".
   8  - New ACM 3.1 software 4.0.1.4.
   9  - New PCM 3.1 software 2.0.0.2.
   10 - The others are version 1.0.3.0.
   11 - "Directional over-current" alarm min. and max. set points have been extended to -300 % and 300 %.
   12 - Only one regulator request is accepted if more have been received.
   13 - It is possible to configure action on "System not OK" alarm.

Corrections:
   1 - Controller types SC, SG and BTB stop synchronising if measure feedback disappears.
   2 – Regulator could freeze if regulators were used in custom logic.
   3 - Regulator continued to regulate after feedback failure on GB.


DU 300

New features:
- Implemented first part of custom stylesheets
- Curves have been added to parameters
- Lamp test
- Identify feature to communication screen
- Units change on display
                      
Changes:
- Navigation and editing in I/O input text is now possible from the keyboard
- Default live data views updated
- Edit line design has been updated
- Updated counter screen to use states
- Default text in keyboard will show resolution
- Live data screens dynamic update (step 1)
- REST version control improvement step 1 (A+B match)
- REST version control improvement step 2 (new REST resource implementation)
- Live data dial meter and vertical bar widgets improved
- Production screen changed to versions screen, production data now visible in about screen
- Added DNS possibility to communication screen
- Added IPv6 address to communication screen
- Live data using REST to build screen and widgets
- Terminal values updated to only show allowed precision
- Updated help screens
                      
Corrections:
- Custom inhibit does no longer clear other inhibit flags
- Placeholder text from previous screen does no longer influence logon screen
- Handling of empty list in pair screen
- Pair screen automatically keeps rescanning for controllers if previously connected to a controller
- Elements in parameters are represented in the same order as in the base unit
- Preparation of lists in the application improved
- Removed dot key from keyboard when value is integer, or precision is zero
- Network off pop-up did not show the first time the display lost connection
- Do not allow user to press OK in empty pair list
- Cardlist serial to be a string instead of integer
- Display reboots after setting up AVR
- No longer showing all functions when function groups is empty
- Cleaned up warnings
- Not able to enable/disable the alarm "Ethernet redundancy broken"
 

1.0.0.3

12/04/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.5.0

 

PPU 300

Corrections:
   1- Trip and stop action did not stop the engine in switchboard mode 
   2- Customlogic inputs was evaluated wrong in scan
   3- Sync. type was changed back from Static to dynamic after a power cycle

 

DU 300

No changes

1.0.0.2

14/03/2017

Corrections:

  • Start and close command now works correctly if “Voltage and frequency OK” timer has been increased.
  • Open and stop command can also stop the engine if breaker is opened, when command has been sent.

 


1.0.0.0

21/12/2016

PPU 300: Initial release

DU 300 ver. 1.0.5.0:

New features:

  • Added placeholder text when the label is completly empty, when you enter an I/O name, the current name of the IO will be shown.
  • Support of 4 line pop-up in the display.
  • Displays the variant on the info/about screen.
  • New pair feature (select base unit).

Changes:

  • DU registration of 4 new languages.
  • DU REST 1.0.2.0 support.
  • Update DU help files.
  • Added REST version to "About screen" in row 3.
  • Made it possible to take pictures of the first pair screen

Corrections:

  • Changed home screen Alarm 8000002 to Alarms 800025 to match the path.
  • Removed two arrows that were shown in parameter groups that was not supposed to be there.
  • Display could have problems, connecting to base units if it was connected in a daisy chain.
  • Making the algorithm responsible for showing/hiding pop-up windows.
  • Updating status text, and diodes in DU is made faster.
  • Crash in start-up sequence removed.
  • Corrected some filtering of allowed functions.
  • Remove illegal references to parameters.
  • Incorrect text shown when valueList had less than 2 elements removed.
  • If alarm screen is detected in the screen history, the current screen is rewound to that alarm screen.
  • DU updating speed improved.
  • Pop-up header characters clip adjusted.
  • IO scale: impossible to select a custom scale with only 1 point.
  • Header text initialised.
  • Pairing pop-up cuts of text on very long labels.
  • Controller for selecting base unit.
  • Appending empty unit to analogue output functions not possible.
  • DU start-up screen has been corrected.
  • Label corrected to "Restart" display instead of "Reset".