Multi-line 2 AGC-4 Mk II Application Software

您即将下载 Multi-line 2 AGC-4 Mk II Application Software

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 6.07.0

与上一版本相比,主要更新如下:

PM compatibility: 1.25.0

New features:

  • EIC: Added Cummins KTA19, Deutz EMR5 Stage V and Perkins Stage V.
  • EIC: Added configurable TSC1 transmission rate and checksum/counter for Generic J1939.
  • EIC: Enable/disable alarm ack. via J1939 (DM11).
  • Extended RMI 20 Points in multi-inputs.
  • Extended mA 17 Points in multi-inputs.
  • M-Logic flags for Enable / Disable for spinning reserve added.
  • Dynamic Frequency Response mode for controlling frequency in situations with excessive amounts of PV-power, added for single generator.
  • Extended EIC wait to start (preheat) support. Introduced M-logic command to inhibit wait to start.
  • EIC: Added support of Scania EMS2 S8 HC Evaporation Status in M-logic and view.
  • Selection of Gov reference for ECU added in menu 15100. Select between nominal frequency or nominal rpm.

Corrections:

  • N + X ON/OFF via digital input or M-Logic corrected.
  • EIC autoviews is not deleted doing power up.
  • Q(U) U-shift regulation could assign a Q reference different than 0 to the AVR regulator when the voltage was inside the deadband. This has been fixed.
  • GOV output was sometimes raising to 100% when GB was closed with static sync. This has been fixed.
  • A genset will now charge a battery with the correct amount during negative PMS setpoints.
  • A genset will now calculate the correct power reference if a battery operating as a energy source is charging from excess PV power.
  • A running DG with its GB closed could react to invalid power management data when changing from a single DG application to a standard application.
  • A mains could issue a start signal to DGs based on invalid power management data when a BTB was powercycled.
  • Idle run stops engine correctly when using Low speed.
版本号 发布日期 描述

6.07.0

11/07/2022

PM compatibility: 1.25.0

New features:

  • EIC: Added Cummins KTA19, Deutz EMR5 Stage V and Perkins Stage V.
  • EIC: Added configurable TSC1 transmission rate and checksum/counter for Generic J1939.
  • EIC: Enable/disable alarm ack. via J1939 (DM11).
  • Extended RMI 20 Points in multi-inputs.
  • Extended mA 17 Points in multi-inputs.
  • M-Logic flags for Enable / Disable for spinning reserve added.
  • Dynamic Frequency Response mode for controlling frequency in situations with excessive amounts of PV-power, added for single generator.
  • Extended EIC wait to start (preheat) support. Introduced M-logic command to inhibit wait to start.
  • EIC: Added support of Scania EMS2 S8 HC Evaporation Status in M-logic and view.
  • Selection of Gov reference for ECU added in menu 15100. Select between nominal frequency or nominal rpm.

Corrections:

  • N + X ON/OFF via digital input or M-Logic corrected.
  • EIC autoviews is not deleted doing power up.
  • Q(U) U-shift regulation could assign a Q reference different than 0 to the AVR regulator when the voltage was inside the deadband. This has been fixed.
  • GOV output was sometimes raising to 100% when GB was closed with static sync. This has been fixed.
  • A genset will now charge a battery with the correct amount during negative PMS setpoints.
  • A genset will now calculate the correct power reference if a battery operating as a energy source is charging from excess PV power.
  • A running DG with its GB closed could react to invalid power management data when changing from a single DG application to a standard application.
  • A mains could issue a start signal to DGs based on invalid power management data when a BTB was powercycled.
  • Idle run stops engine correctly when using Low speed.

6.06.0

18/02/2022

PMS compatibility: 1.25.0

New features:
1- Scania EMS2 S8 Urea/DEF level added to delta alarms.
2- PMS function: block breaker in closed position when one or two faults occur added (menu 8860 and 8870).

Finetuning:
1- TDU can now show the DEF level when Scania EMS2 S8 is used as engine I/F.
2- 32-bit EIC values is shown on new modbus (function 4, reg 26000).
3- IOM works with all supported engine protocols.
4- AMF Overlap is working when modeshift is used.

6.05.0

01/02/2022

PM compatibility: 1.24.2

New features:

  • Added supported ECU types.
  • NTP Support added.
  • Option A20: An external clearing time setting has been introduced in "Advanced Protection" under "Trip parameters".
  • Option A20: Sunspec model 707 and 708 now supported.
  • Option A20: Sunspec model 709 and 710 now supported.
  • Option A20: Sunspec model 703 now supported.
  • Option A20: Sunspec model 704 now supported.
  • Option A20: Sunspec model 705 now supported.
  • Option A20: Sunspec model 711 now supported.
  • Option A20: Q(U) VRef available in the DU-2, TDU and USW data tracer and trending.
  • Option A20: Sunspec model 702 now supported.
  • Option A20: Ability to disable option A20 functionality using menu 9101.
  • Option A20: Sunspec model 701 supported.
  • Option A20: Voltage ride through detection, regulation and protection (based on evaluation of cumulative time).
  • Option A20: Voltage ride through; Suspend regulation drop out time.
  • Option A20: Q(U): Autonomous adjusted VRef is now reset when the DG becomes parallel, when autonomous adjust is enabled, when Q(U) is enabled and when regulation mode is changed over to Q(U).

Changes:

  • Droop curve 1 now uses a more accurate busbar frequency measurement when configured for P(f) operation.
  • Option A20: Fixed cosphi setpoint resolution increased with a factor of 10. Backwards compatibility is not maintained.
  • Option A20: Q(U) open loop time response parameter can now be edited in 10th of a second.

Corrections:

  • No ASC-4 PV irradiance sensor, could make AGC DG's provide inadequate power for mains power export.
  • Cosphi superior setpoints now work with only PV or Battery units on the busbar together with a AGC mains.
  • Volt var handling relative to Vref changed according to tech spec, esp. Autonomous Adj. Vref.
  • Time constant for Vref incorrectly interpreted as open loop time response.
  • When setting parameter #1204 Freq trip type to 'L1 and L2 and L3', the busbar frequency alarms would end up using the generator measurement.
  • Increased measurement inaccuracy at changing frequency could be seen infrequently.

6.04.3

16/11/2021

PM compatibility: 1.24.1

Corrections:

  • Simulating grid frequency via multi-input for droop curve 1 was off by a factor of 10.
  • A change to a different configuration than application 1 using the USW would not persist past a powercycle of the controller.

6.04.2

10/11/2021

PM compatibility: 1.24.1

Corrections:

  • Minimum load was not respected when using droop curve 1.

6.04.1

22/10/2021

Not UL approved version

PM compatibility: 1.24.1

Corrections:

  • Island ramping when loadsharing over CAN or analogue line now works again.
  • Fixed an issue with the EEPROM storage layout.
  • Changing application configuration with jump menu #9160 would not be stored in longterm storage.
  • If the ground relay was enabled and the application configuration was a non PMS single DG, the GB would not open when deloaded.

6.04.0

07/10/2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • New EIC measurement area included with data validation.
  • Support new J1939 priority for exhaust temperatures (CAT).
  • Extended #1230 G f> 3 and #1260 G f< 3 timers to 2000.0 [s].
  • Power ramps improved. 6- Feedforward control to suppress frequency and voltage disturbances in fixed power, reactive power control (in LFSM situations).

Changes:

  • S nominal import/export set points are obsolete. Both are replaced by one S nominal per measurement area.
  • Maximum timer extended to 3200.0 s on a number of protections (AC, digital inputs, MPU, EIC).

Corrections:

  • Translation now works even though no DU-2 is mounted AND only new language is written.
  • Deload TB before GB opens function works correctly in PEAK SHAVING.
  • PMS priority change via M-Logic or Modbus now works correctly.
  • df/dt now operates on the mains side measurements.

6.03.1

13/09/2021

Not UL approved version

PM compatibility: 1.24.1


Corrections:

  • Freeze regulation during FRT now working correctly.

6.03.0

15/07/2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • Two new General Purpose PID´s (GP-PID) 5 and 6 are added. Also added new parameters for all GPIDs (1 to 6) to configure the regulator set point.
  • Support of 3 x 2 A/Os on IOM 220/IOM 230 for GP-PID 1 to 6 is added.
  • Support for John Deere Stage V EIC protocol is added.

Changes:

  • TCP/IP security update.

Corrections:

  • Limit events are added in M-Logic for Extended M-Logic Alarms.
  • "Fuel optimization" and "Fuel optimization + running hours" is now working when using percent values.
  • TDU is now able to change to BLOCK mode (requires TDU version 1.3.7.0).
  • Short circuit supervision (option T1) now includes PV and battery units connected (requires ASC-4 version 4.17.0).
  • EIC transmission rate stability is improved.
  • Default IP address is changed from 192.168.2.2 to 192.168.2.21 to match the TDU default address.

6.02.1

06/05/2021

UL approved version

PM compatibility: 1.23.0

Corrections:

  • Plant management Group Tie redundancy is improved in AUTO and ISLAND plants to secure groups without a start signal to start and stop properly when in need of a redundant unit.
  • Corrected the text for IP, subnet, gateway.
  • Corrected that alarm and battery logs where not shown correctly when the number of entries reached maximum.

6.02.0

06/04/2021

Not UL approved version

PM compatibility: 1.23.0

New features:

  • Support for FPT + Iveco Stage V EIC protocol is added.
  • Four new M-Logic alarms with extended delay are added in menu 3620-3650.
  • VDE 4110 support with MAINS unit in power management is added.
  • Event log entry is added when application setup changes.
  • Support of DVC 550 PSS is added.
  • New GOV and AVR step test are added in parameter group #2970.

Changes:

  • CIO alarms are added to Modbus.
  • Minimum set-point is lowered to 10% for low AC voltage alarms.

Corrections:

  • QSK60G EIC auto view is showing correct values.
  • DVC 550/D550 communication when EIC and Ext. Modules DEIF protocols were selected on two CAN ports is corrected.

6.01.2

15/03/2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • The 4-20 mA output of the option EF5 analogue card now works again.
  • Power factor set point on Modbus is now correctly initialized after a power-up.

6.01.1

12/02/2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • Corrected an issue that caused a mains controller to not be able control the PF setpoint (superior cos phi) on genset controllers.
  • N+X now works when Fuel optimisation is in use.
  • Priority update now works when more than 16 gensets or more than 16 mains are present in a plant configuration.
  • PMS priority data is correct maintained internally in all genset controllers.
  • Breaker feedbacks are properly updated on the I/O status and the I/O setup page.

6.01.0

11/01/2021

UL approved version

PM compatibility: 1.22.0

New features:

  •    Added support for Yuchai Diesel+Gas J1939 protocols.
  •    Addded support for Weichai Diesel+Gas J1939 protocols.
  •    Added support for MAN J1939 protocol.

6-00-0

07/01/2021

Not UL approved version

PM compatibility: 1.22.0

   - Initial release.

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。