iE 350 Application SW (Flexible application)

您即将下载 iE 350 Application SW (Flexible application)

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 2.0.9.0

与上一版本相比,主要更新如下:

2.0.9.0 based on 2.0.8.1

New features

  • Three pump logic routines can now be set up to control the pumping of a substance.
  • Implement ECU diagnostic to enable run coil and ECU power while the engine is stopped.
  • All configuration dependent values are now possible to use in the flexible Modbus.  
    e.g. power supply measurements (dependent on hardware and number of extension racks) can now be mapped to Modbus.
  • Up to 10 ACM3.1 cards allowed in one controller to be used for measurement (preview feature).

Changes

  • EIC: Volvo Penta EMS2.4: "Engine Override Control Mode" changed to "Speed control".  
  • EIC: Volvo Penta EMS2.4: TSC1 will not be transmitted if VP70 is used for regulation. 
  • Modbus timeout increased from 10 sec to 100 sec on iE 250 and iE 350.  
  • Number of possible Modbus connections changed from 20 to 100 on iE 250 and iE 350
  • Added write permission for "Priorities" when controller is in emulation.

Corrections

  • Fixed issue where changes made in the UI were not registered.
  • Fixed issue where the "IO configuration" menu would show empty slots.
  • Fixed issue where tree-structure menu groups could not be collapsed using touch.
  • Fixed issue where configuring a Modbus value to "true" made the value "255" instead of "1".
  • Fixed issue where measurements from multiple ECUs were not shown in UI for e.g. configuring alarms.
  • Fixed issue where display user could not clear DM2 logs.
  • Fixed issue where iE controller could not start without MIO module. 
  • Fixed issue with missing alarm icons.
  • Fixed issue where user could enter parameter values outside of valid range.  
  • Fixed checksum and counter for VP70.
  • Fixed issue where removing network cable would activate system NOK, IO service error and "temperature too high" alarms. 
  • Fixed issue where CODESYS user management files were not included in the backup/restore.
  • Fixed issue where linked outputs in CODESYS was hidden in IO configuration.
  • Fixed issue where the Genset was not de-loading correctly when it was connected to the Mains.
  • Fixed issue where BUS TIE breaker could not de-load and open a ring connected busbar.
版本号 发布日期 描述

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。