Multi-line 300 GPC 300 ver. 1.x.x.

您即将下载 Multi-line 300 GPC 300 ver. 1.x.x.

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 1.0.27.0

与上一版本相比,主要更新如下:

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.20.0

GPC 300

New feature:

• Two new alarms added:
1) "DEIF network has only one connection"
    Default: enabled, Auto ack, No latch (all configurable)
    Action: Warning (hidden)
    Menu location: Communication->DEIF network->
   
       Will trigger when going from 2 to 1 connection are detected.
    - Zero connections is valid for a stand-alone setup.
    - Zero connections will trigger missing all controllers in a system setup.
2) "DEIF network fork detected"
    Default: enabled, Auto ack, No latch (all editable)
    Action: Warning (hidden)
    Menu location: Communication->DEIF network->
    Will trigger when 3 or more connections are detected.

Corrections:

• Fixed issue where the ROCOF set point and triggered value were not shown on the alarm page (DU300 and PICUS).
• Fixed issue where "Data loss on DEIF network" would incorrectly trigger at start-up.
• Fixed issue where a redundancy supervision alarm did not trigger when external network equipment was used.
• Increased number of missing controller alarms shown.
• Fixed issue with controller crashing doing backup.
• Fixed issue where a controller performed an unwanted restart due to rare issue in Modbus.
• Fixed issue where reading IO status on Modbus could cause unwanted restart of the application software.

 

版本号 发布日期 描述

1.0.23.0

08/03/2023

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.20.0

GPC 300

New feature:

  • New variant that has a mains with mains breaker and tie breaker.
  • Added emulation for single gensets.
  • Added the possibility to read dynamic section status in CODESYS.
  • Added PMS power measurement data.

Changes:

  • Changed the maximum value for breaker open failure delay to 60 seconds.
  • Changed the maximum value for breaker close failure delay to 60 seconds.
  • Added PMS power measurement data.
  • Selection of "Phase-Phase" / "Phase-Neutral" on selected voltage protections are always shown.

Corrections:

  • Emulation now works with fixed power, while mains is exporting (negative kW values on mains).
  • Breaker operation counter now increments correctly in emulation.
  • Fixed issue with no tags shown in HMI for AC setup parameter.
  • Improved backup percentage count in PICUS.
  • Missing texts have been added.
  • It is now possible to access the DM2 log from PICUS.
  • Fixed missing IOM3.4 support.
  • Analogue AVR now works in emulation.
  • Fixed an issue with external breaker feature in emulation.
  • Fixed an issue with using the stop command from switchboard in emulation. This would not stop the engine when running in parallel.
  • Mains variants have regulator control available in emulation.
  • Close failure can now be emulated.
  • The response time for the trip breaker output can exceed 100ms if the configuration has been done in a particular order and the controller has not been power cycled.
  • Fixed issue where there could be Hz on the generator measurements in emulation when the engine was stopped.
  • Fixed issue with MPU wire break. It is now working.
  • Fixed issue where the states in emulation were preserved when emulation was not enabled.

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

1.0.21.0

07/10/2022

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

GPC 300

New feature:

  • Added support for multiple applications with a parameter to select active application and custom plant name. (Not supported by PICUS.)

Corrections:

  • Fixed issue where I/O parameter configuration was passed on from one external breaker or a heavy consumer on the single line to another when during commissioning. I/O configuration and parameters are not reset.
  • Fixed issue where manual regulation didn't work in emulation.
  • Fixed issue where analogue regulation was unstable in emulation.
  • Fixed issue with GAM3.2 not working in emulation.
  • Fixed issue with incorrect regulator mode when a single genset (GB only) connected to mains.
  • Actual Power total in % is now showing on DU-300 (Live data) and in PICUS.
  • Fixed issue with external voltage offset in load sharing not working.

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

1.0.20.0

09/09/2022

This software package consist of:

  • Multi-line 300, GPC 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

GPC 300

First release

DU 300

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。