Multi-line 2 GCU 100 Application Software series 1.xx.

您即将下载 Multi-line 2 GCU 100 Application Software series 1.xx.

您已选择下载我们的软件。

几秒钟内,您将收到一封包含下载链接的电子邮件。

如果使用软件有问题,请联系support@deif.cn.

诚挚的祝福,

DEIF A/S

本软件受DEIF A/S版权保护。请点击上述链接可查阅DEIF A/S版权和许可协议(EULA)。

本软件适用于以下DEIF产品

您即将下载 1.02.1

与上一版本相比,主要更新如下:

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)
版本号 发布日期 描述

1.02.1

15/03/2016

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)

1.02.0

03/02/2016

New features:

  • Contrast offset added in parameter 9152.
  • PT 1000 sensors introduced in multi-input 6 and multi-input 7.
  • Several events and limits added to M-Logic.
  • Added one additional battery low alarm (parameter 4950).
  • Inhibits can be set in battery low/high menu (parameter 4950/4960/4970).
  • Oil renewal feature introduced.
  • Battery voltage column now available in every entry in the log information in the DEIF Utility Software.
  • Added three freely translatable texts in the view lines.
  • Added support of ADEC CAN open, shutdown override.
  • Added EIC manual speed regulation

 

Changes:

  • Multi-inputs made linear in application emulation.
  • Parameter ranges in parameters 1150 and 1160 extended.
  • Increased parameter 2112 maximum value.
  • Extended maximum limit in start on time, parameter 6183.
  • Hz/V Ok parameter 6821 minimum value now extended to zero.
  • Extended fuel fill check timer (parameter 6553).
  • Made it possible to enable/disable fuel fill check (parameter 6553).
  • Made it possible to use auto acknowledge on Ext. Comm. Error parameter.
  • Start attempt maximum limits changed. Extended stop timer minimum limit changed.
  • Language translation changed. From now on it is not possible to select a different font.  The two fonts are now merged together, and containing all previously used characters. New characters are added. If any unsupported signs are written to the device the signs  will appear as ' ' (space).
  • Three RMI sensor curves added. One for each RMI type.  It will be possible to choose them in channel 10460, 10630 and 10800 by selecting "Sensor type 4" in the DEIF Multi-line 2 Utility Software v.3.
  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Stop coil did not activate when start sequence was aborted.
  • Inhibit evaluation added to a number of AC alarms.
  • Missing digit to running hours corrected.
  • Sign of display values between -1.0...0.0 with one or two decimals shown correctly.
  • Missing EIC values in analogue delta alarms added.
  • Measurement through the MPU input caused periodical peaks in the RPM measurement, which could cause an unwanted trip of the generator breaker.
  • Change of AC scale caused several energy counter views to be displayed with wrong decimal point and unit.
  • M-Logic line combination misinterpretation corrected.
  • Application emulation couldn't start properly with breaker and engine commands selected as inactive.
  • The lower inhibit level for phase sequence error increased from 30 % to 70 % of nominal voltage.
  • PT sensor offset parameters now corrected to compensate for the cable resistance.
  • Unit and MTU ADEC(SAM) communication not started during certain power supply situations - corrected. (Updated correction to avoid start request after communication has been reestablished).
  • M-Logic command "Start and Close GB" was ignored during cool down.
  • SCANIA EMS2 correction of start/stop.
  • Clock synchronise over Modbus was causing the service timer to offset its current timer value - corrected.
  • Configuration of output relays corrected, so all functions can be connected to all available relays.
  • Selection of multi-inputs for fuel pump logic corrected.
  • Fuel pump relay could activate at power-up of the controller before fuel level measurement has settled.
  • Several Modbus (option H2) addresses were not working - corrected.
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Idle run timer now resets at each start attempt.
  • View lines: Run absolute and energy total corrected.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active.
  • Running hour counter could reset unintendedly - corrected.
  • Running hour counter could reset unintendedly at power cycle - corrected.
  • Scania EMS2 KWP2000 log clear now possible.
  • Exhaust gas temperature - right/left was not shown correctly in display.
  • Storage of service timer values during reset corrected.
  • Relays could activate under boot sequence - corrected.

1.01.0

23/02/2015

New features:

  • Common alarm
  • Siren

Changes:

  • Relay 3 default setting changed from Horn to Not used

Corrections:

  • The functionality of not showing alarm in case of combination of the alarms used  in relays has been corrected
  • Idle run activation through digital input and reactivation after stop button functions have been corrected
  • Idle run function corrected

1.00.2

01/09/2014

Corrections:

  • Relay channel error after power up corrected
  • Missing menu for blackout control added
  • Phase-phase / phase-neutral selection for protections corrected
  • Parameter 3410 password corrected
  • MTU Smart Connect engine protocol updated
  • Forcing GB feedbacks in emulation corrected
  • Reactive power for L1L3L2 AC configurations corrected
  • Parameter 1201 + 1202 only available for 3-phase AC configurations 

1.00.1

26/11/2013

Corrections:

  • Day of week is not adjusted when the date is changed - Corrected
  • Several menu texts were not using translations - Corrected
  • ECU 100 (GCU 111 & 112): Not able to start on D.I Remote Start - Corrected

1.00.0

01/05/2013

  • First release

在此页面,您可以下载产品的更新软件,并使用各种实用工具和附加组件设置、检测故障和配置产品。

请注意,用户无法更新我们的所有产品。同时也不是所有产品都配有实用工具。因此,本页的软件列表不能视为DEIF产品的概述。

DEIF将登记您注册的下载邮箱地址,以便在未来需要时发送有关的更新信息。

DEIF不对产品更新失败或使用实用工具造成的任何后果负责。DEIF A/S也不对软件升级导致的产品行为变化的后果负责。用户始终有责任在调试前确保正确的设置和配置。请在更新产品之前查阅软件的更新日志。

www.deif.cn软件下载许可协议

下载的软件仍是DEIF的财产。本软件不得用于商业目的分发, 不得全部或部分更改或重复使用,也不得出售给任何第三方。

最新版本,功能齐全

我们始终建议您安装最新版本的软件,以充分利用您的DEIF产品。

所有更新的软件都可以从www.deif.cn->支持->下载->软件栏目下下载。

如果您在查找产品的相关软件时有任何疑问或问题,请随时致电丹控电气(上海)有限公司,电话: +86 21 68796200,或者发送电子邮件至support@deif.cn, 我们随时为您服务。